Transformer load check
Enter the transformer's rating in VA from its label or manual and, for each kind of fixture, how many there are and the VA each one is rated at. The check adds them up and shows the total as a share of the rating. Every number comes from what you type and the formula below.
Worked example: total fixture load
VA
- Share of the rating
- %
- Below the rating by
- VA
- Fixtures counted
- Rating entered
- VA
Worked example with example numbers: 54.5 VA from 11 fixtures is 36.3% of a 150 VA rating.
| Row | Fixtures | VA each | Row total |
|---|---|---|---|
| 1 | 8 | 4 | 32 VA |
| 2 | 3 | 7.5 | 22.5 VA |
Estimate only. The total is the sum of the ratings you typed, not a measurement. This page sets no limit of its own: compare the result with what the transformer's manual says about its rating.
How the total is worked out
Row total = N × S
Total load = sum of all row totals
Share of the rating = total load ÷ R × 100
Difference = R − total load
- N is the number of fixtures in a row, a whole number from 1 to 10,000.
- S is the VA rating of one of those fixtures, from its documentation, greater than zero and up to 10,000 VA.
- R is the transformer's VA rating, from its label or manual, from 1 to 100,000 VA.
- Rows left empty are skipped. A row with only one of its two numbers is refused until both are filled in or both are cleared.
Assumptions and limits
- VA (volt-amperes) and watts are not the same thing. VA is apparent power, voltage times current. The check adds up VA figures, so enter the VA figure where a fixture's documentation gives one.
- If the transformer's or a fixture's documentation lists only watts, the maker is the place to ask how that figure compares with VA. Entering watts in place of VA makes the total and the share approximations.
- The total is the sum of the ratings you typed. It is not a measurement, and the check knows nothing about any particular transformer or fixture.
- The check sets no limit of its own and gives no pass or fail. How far a transformer may be loaded is set by its maker: compare the result with the transformer's manual.
- Installation follows the maker's manual and local rules.